Universal 24 Vac, Standard Opening, Intermittent Pilot Gas Valve with 1/2 in. x 1/2 in. inlet/outlet

VR8245M2530/U

Universal 24 Vac, Standard Opening, Intermittent / Direct Ignition Gas Valve 1/2 x 1/2". Set 3.5" WC

  • Product Info
  • Literature
  • Accessories & Replacement Parts

Overview

Universal electronic ignition combination gas control for use with direct spark ignition, hot surface ignition or intermittent pilot ignition in 24 Vac, gas-fired appliances, with capacities from 20 to 200 cfh (VR8245M) or 30 to 415 cfh (VR8345M).

Features

  • Control includes manual valve, two automatic operators, pressure regulator, pilot adjustment, pilot plug and ignition adapter.
  • Replaces many IP, HSI, or DSI gas control.
  • For use with natural or manufactured gas or LP gas.
  • Includes converter kit to adapt from natural to LP gas.
  • Compact size.
  • All adjustments and wiring connections accessible from top of control.
  • Four-inch swing radius allows easy rotation into position inside the tightest furnace vestibules.
  • Clearly marked, keyed terminal block allows quick attachment of wires and IP/DSI/HSI jumper.
  • Internal inlet screen blocks contaminants in gas line from entering valve.

Product Specifications

Application
Single Stage
Dimensions (in.)
5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
Dimensions (mm)
135 mm high x 104 mm wide x 69 mm deep
Includes
Natural to LP Conversion Kit; One 1/2" x 3/8" reducer bushing
Item Type
Product
Mounting
0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL Component Recognized MCCZ2.MH5323
Approvals, Canadian Standards Association
CSA International: 112395
Tradeline Value
Universal
Electrical Connections
1/4 in. quick-connect male terminals
Voltage
24 Vac
Operating Temperature Range (F)
-40 F to +175 F
Operating Temperature Range (C)
-40 C to +79 C
Body Pattern
Straight-through
Opening Characteristics
Standard Opening
Pressure Ratings (psi)
1/2 psi
Pressure Ratings (kPa)
3.5 kPa
Inlet/Outlet Size (in.)
1/2 in. x 1/2 in.
Pilot Gas Outlet
Compression fitting for 1/4 in. OD tubing
Pressure Tapping
1/8 in. NPT with plug
Type of Fuel
Natural (LP with included conversion kit)
Capacity (kBtuh)
At 1 in. wc p.d.-- 150,000 BTUh: 20,000 BTUh minimum: 200,000 BTUh maximum Natural Gas
Pressure Regulator
Standard
Pressure Regulator Setpoint (in. wc)
3.5 in. wc
Pressure Regulator Setpoint (kPa)
0.9 kPa
Ignition Type
Direct Ignition; Intermittent Pilot

Accessories

393691/U

Single Stage Natural to LP Gas Conversion Kit. 8" to 12" adjustment range. Includes regulator spring, o-ring, adjustment screw and cap screw

395253-1/U

Single Stage LP to Natural Gas Conversion Kit. 5" to 7" WC adjustment. Includes regulator spring, o-ring, adjustment screw and cap screw

392877/U

1/4 inch barbed vent fitting

390427E/U

Two 3/4 x 1/2 in. reducer bushings

390427B/U

Envelop with Reducer bushing (1/2 in.to 3/8 in. npt)

390427A/U

One 3/4 x 1/2 in. reducer bushings

393690-15/U

Flange Kit bag assembly, includes 3/4 inch elbow flange, O-ring, 9/64 inch hex screws and 9/64 inch hex wrench

393690-13/U

Flange Kit bag assembly, includes 1/2 inch elbow flange, O-ring, 9/64 inch hex screws and 9/64 inch hex wrench

393690-4/U

Flange Kit bag assembly, includes 3/4 inch straight flange, O-ring, 9/64 inch hex screws, and dust plug.

396025/U

Two Stage LP to Natural Gas Conversion Kit. 3" to 5" adjustment range.

396021/U

Two Stage Natural to LP Gas Conversion Kit. 8" to 11" adjustment range.

394588/U

Single Stage LP to Natural Gas Conversion Kit. 3" to 5" adjustment range. Includes regulator spring, o-ring, adjustment screw and cap screw