Skip Ribbon Commands
Skip to main content
SharePoint
Login or Register to view pricing and order.
Item 7 Of 8
High or low limit surface mount controller with SPDT, operating range 65-200F, factory stop at 200F
High or low limit surface mount controller with SPDT, operating range 65-200F, factory stop at 200F

L6006C1018/U

High or low limit surface mount controller with SPDT, operating range 65-200F, factory stop at 200F

  • Product Info
  • Literature

Overview

Aquastat® Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.

Features

  • Totally enclosed Micro Switch™ snap-acting switches operate on temperature rise to set point.
  • Visible control point scale and external adjustment screw permit easy setting.
  • Horizontal or vertical insertion of the sensing element.
  • Direct, well immersion, or surface mounting of the sensing element available.
  • Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications.
  • Select direct or well immersion models include heat-conductive compound.
  • Select models have wells.

Product Specifications

Hazmat Information
UN 1294, TOLUENE, 3, II
Application
Circulator Control and High Limit or Low Limit
Dimensions (in.)
Case--5 5/8 in. high x 2 in. wide x 2 3/4 in. deep
Dimensions (mm)
Case--136 mm high x 51 mm wide x 70 mm deep
Temperature Range (F)
Maximum Ambient--150 F
Temperature Range (C)
Maximum Ambient--66 C
Includes
Stop factory-set at 200 F (93 C)
Mounting
Horizontal or Vertical or Surface mounting
Electrical Ratings
Millivolt--0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 5.1A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 30.6A @ 240 Vac
Approvals, Underwriters Laboratories Inc.
UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
Approvals, Canadian Standards Association
Certified: File No. LR95329-1
Operating Temperature Range (F)
65 F to 200 F
Operating Temperature Range (C)
18 C to 93 C
Bulb Size (in.)
3/8 in. x 2 7/8 in. copper
Bulb Size (mm)
10 mm x 73 mm copper
Differential Temperature (F)
5 F to 30 F adj.
Differential Temperature (C)
3 C to 17 C adj.
Switching Action
SPDT

Marketing Collateral

Sales/Promotional Materials-Cross Reference Guide for Residential Combustion Heating and Cooling Parts (English)

Wiring-Typical oil-fired gravity system

Wiring-Typical systems with 120 volt electric heat primaries

Wiring-Typical Powerpile System wiring diagram

Wiring-Typical oil-fired hydronic heating system

Wiring-Typical gas-fired system with domestic hot water

Wiring-Operation of L6008G

Wiring-Operation of L4008L

Wiring-L6008A used to control cooling equipment and indicating light.

Wiring-Typical wiring hookup

Wiring-Typical connection diagram for an oil fired hydronic heating system

Wiring-Typical oil-fired hydronic system with domestic hot water.

Dimension-Approximate immersion well dimensions in in. (mm) for all models except L4006C a

Dimension-Approximate boiler fitting and bulb dimensions in in. (mm) for L4006C and L6006B

Dimension-Approximate installation dimensions in in. (mm) for remote bulb models

Dimension-Approximate case installation dimensions in in. (mm) for direct insertion models

Dimension-Approximate installation dimensions in in. (mm) for surface mount models.

Dimension-Aquastat(r) Controller

Technical Documents

Installation Materials-Installation Instructions for L6006, L6007 Aquastat Controllers (English)

Installation Materials-Installation Instructions for L6006, L6007 Regulateurs Aquastat- (French) - Legacy Product Document

Product Data and Specifications-Product Data for L4006,7,8; L6006,7,8 Aquastat® Controllers (English)

Maintenance/Product Reference Materials-Residential Combustion Application Selection and Cross-Reference Guide (English)