Overview
The humidity resistant, Fan Coil Valve Actuators are used in conjunction with VU52, VU53 and VU54 valves for controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors.
Features
- Compact construction for easy installation.
- Fits under the cover of most baseboard convectors with actuator fitted to valve body.
- One-button, quick release. Secure 3-point, metal latch to valve body.
- Spring return operation.
- Stainless steel case and aluminum cover. Rust-proof nickel-plated motors available.
- Line or low voltage, rust-resistant motors.
- Manual opener for installation and valve operation on power failure.
- Valve returns to automatic position when power is restored.
- Actuator may be reinstalled or serviced without draining the system or disassembling the valve.
- Slotted conduit hole for faster wiring.
Product Specifications
- Application
- For controlling the flow of hot or chilled water in commercial HVAC equipment such as fan coil units, terminal reheat coils and convectors
- Dimensions (in.)
- 2 3/8 in. high, 3 1/2 in. wide, 2 3/8 in. wide
- Dimensions (mm)
- 62 mm high, 88 mm wide, 60 mm deep
- Used With
- 2-way NO (VU52) or 3-way VU valve body (VU54)
- Materials
- Stainless Steel Case, Aluminum Cover
- Item Type
- Product
- Frequency
- 50 Hz; 60 Hz
- Approvals, Canadian Standards Association
- Certified C/US File No. LR1322
- Electrical Connections
- Leads
- Supply Voltage
- 24V
- Power Consumption
- Driving-- 6 Watts
- Ambient Temperature Range (C)
- 1 C to 52 C ambient at 93 C Fluid
- Ambient Temperature Range (F)
- 34 F to 125 F ambient at 200 F Fluid
- Electrical Connections (in.)
- 6 in.
- Electrical Connections (mm)
- 0.15 m
- Internal Auxiliary Switch
- 0
- Fluid Temperature (C)
- 94 C
- Fluid Temperature (F)
- 200 F
- Actuator Type
- Valve
- Control Signal
- Two position; SPST
- Fail Safe Mode
- Spring Return
- Stroke (in.)
- 45 deg.
- Timing, Nominal
- Driving @ 60 Hz (sec)-- 15 sec maximum
- Spring Return Timing
- Nominal-- 6 sec
- Maximum Differential Pressure Ratings (Close-off) (psi)
- Depends on Cv rating of valve
- Maximum Differential Pressure Ratings (Close-off) (kPa)
- Depends on Cv rating of valve
- Manual operation
- Lever