Skip Ribbon Commands
Skip to main content
SharePoint
Login or Register to view pricing and order.
  • Product Info
  • Literature

Overview

Photoconductive flame sensing device for sequencing oil burner systems.

Features

  • On flame failure, the light sensitive cadmium sulfide cell, in conjunction with flame sensing circuitry, causes the Protectorelay® control to shutdown the main oil burner.
  • Glass-to-metal hermetic seal in plug-in cell prevents deterioration by humidity, soot or oil fumes.
  • Replaceable CAD Cell

Product Specifications

Application
Oil fired burners
Dimensions (in.)
5/8 in. high x 1 in. long x 1/2 in. wide
Dimensions (mm)
16 mm high x 25 mm long x 13 mm w
Used With
R4166, R4184, R8182, R8184, R8185, R8404, R8991, R7997, R7184, R7284
Item Type
Product
Mounting
Type J bracket
Approvals, Underwriters Laboratories Inc.
UL Listed: File no. MP268, Vol. 39, Sec. 1, Guide MCCZ
Approvals, Canadian Standards Association
CSA Component Listed: File no. LR95329-1
Electrical Connections
lead wires: NEC Class 1
Replacement Parts
120320 Replacement Cad Cell. 7.5 mA minimum sensitivity at 2 ft. candles; 130367 Replacement Cad Cell. 12.0 mA minimum sensitivity at 2 ft. candles.
Power Consumption
7.5 mA
Ambient Temperature Range (C)
60 C maximum
Ambient Temperature Range (F)
140 F maximum
Lead Length (in.)
30 in.
Lead Length (mm)
762 mm
Sensitivity
Minimum sensitivity at 2 ft candles
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.