Overview
Photoconductive flame sensing device for sequencing oil burner systems.
Features
- On flame failure, the light sensitive cadmium sulfide cell, in conjunction with flame sensing circuitry, causes the Protectorelay® control to shutdown the main oil burner.
- Glass-to-metal hermetic seal in plug-in cell prevents deterioration by humidity, soot or oil fumes.
- Replaceable CAD Cell
Product Specifications
- Application
- Oil fired burners
- Dimensions (in.)
- 1 7/8 in. high x 1 in. long x 1/2 in. wide
- Dimensions (mm)
- 47 mm high x 25 mm long x 13 mm wide
- Includes
- Type "E" mounting bracket and fuel line adaptor
- Used With
- R4166, R4184, R8182, R8184, R8185, R8404, R8991, R7997, R7184, R7284
- Item Type
- Product
- Mounting
- Type R bracket
- Approvals, Underwriters Laboratories Inc.
- UL Listed: File no. MP268, Vol. 39, Sec. 1, Guide MCCZ
- Approvals, Canadian Standards Association
- CSA Component Listed: File no. LR95329-1
- Tradeline Value
- Tradeline
- Electrical Connections
- lead wires: NEC Class 1
- Replacement Parts
- 120320 Replacement Cad Cell. 7.5 mA minimum sensitivity at 2 ft. candles; 130367 Replacement Cad Cell. 12.0 mA minimum sensitivity at 2 ft. candles.
- Power Consumption
- 12 mA
- Ambient Temperature Range (C)
- 60 C maximum
- Ambient Temperature Range (F)
- 140 F maximum
- Lead Length (in.)
- 60 in.
- Lead Length (mm)
- 152.4 cm
- Sensitivity
- Minimum sensitivity at 2 ft candles
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.