Overview
Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.
Features
- High limit opens burner circuit only.
- Select models include transformer and accessory terminals for adding a remote low limit controller.
- Case available for horizontal or vertical mounting.
- Requires a 24 Vac thermostat with heat anticipator set at 0.2A.
- TRADELINE models include well adapter, tube of heat conductive compound and range stops..
Product Specifications
- Hazmat Information
- UN 1294, TOLUENE, 3, II
- Application
- High Limit
- Dimensions (in.)
- 6 1/8 in. high x 4 5/16 in. wide x 3 1/8 in. deep
- Dimensions (mm)
- 156 mm high x 110 mm wide x 79 mm deep
- Maximum Safe Operating Pressure (psi)
- Immersion Well: 255 psi
- Maximum Safe Operating Pressure (kPa)
- Immersion Well: 1757 kPa
- Temperature Range (F)
- Maximum--150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load
- Temperature Range (C)
- Maximum--66 C with 1.2 A 24 V load; 25 C with 1.4 A 24 V load
- Includes
- Molex® plug for use with vent damper, includes heat-conductive compound.; Molex(r) plug for use with vent damper, includes heat-conductive compound.
- Mounting
- Vertical Mount
- Electrical Ratings
- Low Voltage: 0.8 A max. @ 24 Vac; 0.25 A @ 0.25 to 12 Vdc; At Locked Rotor-- 44.4A @ 120 Vac: 22.2A @ 240 Vac
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2.
- Approvals, Canadian Standards Association
- Certified: File No. LR95329-1
- Tradeline Value
- Tradeline
- Electrical Connections
- Quick-Connect / Screw
- Operating Humidity Range (% RH)
- 0 to 95% RH, non-condensing
- Voltage
- 120 Vac
- Operating Temperature Range (F)
- High Limit-- 180 F to 240 F
- Operating Temperature Range (C)
- High Limit-- 82 C to 116 C
- Differential Temperature (F)
- 15 F fixed
- Switching Action
- SPST: High Limit & Circulator
- Anticipator Setting
- 0.2 A
- Capillary Length (in.)
- 4 1/2 in.
- Insulation Depth (in.)
- 1 1/2 in. to 3 in. less well
- Insulation Depth (mm)
- 38 mm to 76 mm less well
- Capillary Length (mm)
- 114 mm
- Electrical Ratings, Burner
- At Full Load-- Low Voltage: 0.8 A max. @ 24 Vac: Line Voltage: 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- Line Voltage: 44.4 A @ 120 Vac: 22.7 A @ 240 Vac
- Electrical Ratings, Circulator
- At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.