Overview
Immersion type Aquastat controller and oil burner primary control provides high limit and low limit/circulator control for oil-fired hydronic heating systems.
Features
- Use in intermittent ignition applications.
- Capable of zone control with zone valves.
- Circulator zone control with ZC and ZR terminals on R8182D,E,H,J. 8*Flame failure during the running cycle results in a 45 second attempt to restart.
- If unsuccessful, safety shutoff occurs, requiring manual reset before burner can be restarted.
- R8182D,E,F mount directly on burner; R8182H,J mount on 4 x 4 in. junction box and include 5 ft (1.5 m) armored capillary with remote sensor.
- C554A Cadmium Sulfide Flame Detector and a 24 Vac thermostat required.
Product Specifications
- Hazmat Information
- UN 1294, TOLUENE, 3, II
- Dimensions (in.)
- 7 1/8 in. high x 5 1/4 in. wide x 3 7/16 in. deep.
- Dimensions (mm)
- 181 mm high x 133 mm wide x 87 mm deep.
- Maximum Safe Operating Pressure (psi)
- 200 psi on immersion well; 100 psi direct immersion.
- Maximum Safe Operating Pressure (kPa)
- 1378 kPa on immersion well; 90 kPa direct immersion.
- Temperature Range (F)
- Maximum--250 F at element
- Temperature Range (C)
- Maximum--121 C at element
- Includes
- Auxiliary ZC and ZR terminals may be used to provide circulator zone control through an R845A Switching Relay. Heat-conductive compound and vertical case.
- Mounting
- Vertical Mount
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: File No. listed: MP268, Vol. 3,4 (R8182D,E,F), Vol. 37 (R8182H,J), Sec. 1.
- Approvals, Canadian Standards Association
- Certified: File No. LR95329-1
- Tradeline Value
- Tradeline
- Operating Humidity Range (% RH)
- 0 to 95% RH, non-condensing
- Power Consumption
- 9 W
- Voltage
- 120 Vac
- Operating Temperature Range (F)
- High Limit-- 130 F to 240 F; Low Limit-- 110 F to 220 F
- Operating Temperature Range (C)
- High Limit-- 54 C to 116 C; Low Limit-- 43 C to 104 C
- Differential Temperature (F)
- High limit: 10 F fixed; Low limit/circulator: 10 F to 25 F adj.
- Timing
- Safety Switch-- 45 sec
- Anticipator Setting
- 0.2 A
- Insulation Depth (in.)
- 1 1/2 in.
- Insulation Depth (mm)
- 38 mm
- Electrical Ratings, Ignition
- 360 VA
- Electrical Ratings, Burner
- At Full Load-- 4.4 A @ 120 Vac; At Locked Rotor-- 26.4 A @ 120 Vac
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.