Skip Ribbon Commands
Skip to main content
SharePoint
Login or Register to view pricing and order.
  • Product Info
  • Literature

Overview

Provide intermediate switching of a line voltage device from a low voltage controller.

Features

  • Integral transformer provides low voltage power for control circuit.
  • The RA832A is a TPST relay. One relay pole is designed for low voltage or millivoltage (PowerPile®) auxiliary load. Two other relay poles are for line voltage loads.

Product Specifications

Application
Provide intermediate DPST switching of a line voltage device from a low voltage controller.
Dimensions (in.)
5 1/4 in. high x 4 1/4 in. wide x 2 5/16 in. deep
Dimensions (mm)
133 mm high x 108 mm wide x 59 mm deep
Includes
Integral transformer, enclosure
Item Type
Product
Electrical Ratings
Maximum Input-5.0 W
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
Listed: File No. E4436, Guide No. XAPX
Approvals, Canadian Standards Association
Certified: File No. LR1620
Tradeline Value
Tradeline
Electrical Connections
Control Circuit- 2-Wire
Temperature Ratings (C)
46 C maximum ambient for 60 Hz. 41 C maximum ambient for 50 Hz.
Temperature Ratings (F)
115 F maximum ambient for 60 Hz. 105 F Max. Ambient for 50 Hz.
Switching
DPST; one pole line voltage, the other low voltage or millivolt
Pilot Duty Ratings
Secondary-- 50 VA @ 24V
Contact Ratings (AFL)
At 120 Vac-- 7.4A AFL; 240 Vac-- 3.7A
Contact Ratings (ALR)
At 120 Vac-- 44.4A; 240 Vac-- 22.2A
Contact Ratings (resistive)
At 120 Vac-- 10A; 240 Vac-- 6.0A
Input Voltage
240V
Coil Ratings Voltage
24 Vac
Coil Ratings Current
0.4A
Electrical Ratings, Contacts
Maximum connected load is 2000 VA (120 Vac to 240 Vac); Secondary DC Rating-- 1A @ 12 Vdc; Secondary millivolt Rating-- 300 mA min. @ 750 mV
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.