Overview
Provide intermediate switching of a line voltage device from a low voltage controller.
Features
- Integral transformer provides low voltage power for control circuit.
- The RA832A is a TPST relay. One relay pole is designed for low voltage or millivoltage (PowerPile®) auxiliary load. Two other relay poles are for line voltage loads.
Product Specifications
- Application
- Provide intermediate DPST switching of a line voltage device from a low voltage controller.
- Dimensions (in.)
- 5 1/4 in. high x 4 1/4 in. wide x 2 5/16 in. deep
- Dimensions (mm)
- 133 mm high x 108 mm wide x 59 mm deep
- Includes
- Integral transformer, enclosure
- Item Type
- Product
- Electrical Ratings
- Maximum Input-5.0 W
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- Listed: File No. E4436, Guide No. XAPX
- Approvals, Canadian Standards Association
- Certified: File No. LR1620
- Tradeline Value
- Tradeline
- Electrical Connections
- Control Circuit- 2-Wire
- Temperature Ratings (C)
- 46 C maximum ambient for 60 Hz. 41 C maximum ambient for 50 Hz.
- Temperature Ratings (F)
- 115 F maximum ambient for 60 Hz. 105 F Max. Ambient for 50 Hz.
- Switching
- DPST; one pole line voltage, the other low voltage or millivolt
- Pilot Duty Ratings
- Secondary-- 50 VA @ 24V
- Contact Ratings (AFL)
- At 120 Vac-- 7.4A AFL; 240 Vac-- 3.7A
- Contact Ratings (ALR)
- At 120 Vac-- 44.4A; 240 Vac-- 22.2A
- Contact Ratings (resistive)
- At 120 Vac-- 10A; 240 Vac-- 6.0A
- Input Voltage
- 240V
- Coil Ratings Voltage
- 24 Vac
- Coil Ratings Current
- 0.4A
- Electrical Ratings, Contacts
- Maximum connected load is 2000 VA (120 Vac to 240 Vac); Secondary DC Rating-- 1A @ 12 Vdc; Secondary millivolt Rating-- 300 mA min. @ 750 mV
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.