Skip Ribbon Commands
Skip to main content
SharePoint
Login or Register to view pricing and order.
  • Product Info
  • Literature

Overview

The SmartValve® System Controls combine gas flow control and electronic intermittent pilot sequencing functions into a single unit. The Q3450 or Q3480 Pilot hardware supplies the low voltage igniter, flame sensor and pilot burner. These ignition system controls provide all gas ignition safety functions by controlling gas flow, ignition source, and a 120 Vac or 240 Vac combustion air blower. The controls also monitor the appliance airflow proving switch and limit string to assure proper appliance operation, and provide prepurge, postpurge, and timed trial for pilot ignition with 100 percent shutoff and continuous retry. Includes a diagnostic LED indicates system status.

Features

  • These controls communicate directly with an electronic fan timer (ST9160 Electronic Fan Timer for single stage applications; ST9162 Electronic Fan Timer for two-stage applications) in typical forced warm air furnace applications.
  • It can directly interface with the appropriate power supplies and a system thermostat for additional appliance applications.
  • When controlled directly by a thermostat, these controls do not provide a postpurge function, because power to the control is removed when the thermostat call for heat ends.
  • The Systems are suitable for a wide range of fan-assisted combustion gas-fired appliances including furnaces, rooftop furnaces, boilers, unit heaters, infrared heaters, water heaters and commercial cooking appliances.

Product Specifications

Dimensions (in.)
3.2 in. wide x 4.9 in. high x 4.1 in. long
Dimensions (mm)
81 mm wide x 124 mm high x 104 mm long
Includes
Two 3/4 x 1/2 in. reducer bushings; Natural to LP Conversion Kit
Item Type
Product
Mounting
0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
Electrical Ratings
24 Vac
Frequency
50 Hz; 60 Hz
Approvals, Canadian Standards Association
CSA International: 112395
Tradeline Value
Universal
Flame Failure Response Time (sec)
1.6 sec @ 3 µA
PrePurge
15 seconds
PostPurge
30 seconds
Ambient Temperature Range (C)
-40 C to +79 C
Ambient Temperature Range (F)
-40 F to +175 F
Ignition System Type
Intermittent Hot Surface Pilot Ignition
Ignition Sequence
Intermittent Pilot
Type of Gas
Natural
Flame Sense
HSI
Ignition Source
Pilot
Ignition Trials To Lockout
continuous retry
Ignition Trial Time (sec)
90 sec
Typical Ignition Hardware
Q3450; Q3480
Body Pattern
Straight-through
Opening Characteristics
Standard
Pressure Regulator Setting (psi)
3.5 in. WC
Pressure Regulator Setting (kPa)
0.87 kPa
Pressure Ratings (psi)
1/2 psi
Pressure Ratings (kPa)
3.5 kPa
Inlet/Outlet Size (in.)
3/4 in. NPT x 3/4 in. NPT.
Pilot Gas Outlet
Yes
Capacity (ft³/hr)
Maximum at 1 in. P.D.--300 ft³/hr; Maximum--415 ft³/hr; Minimum--30 ft³/hr
Capacity (m³/hr)
Maximum at 1 in. P.D.--8.5 m³/hr; Maximum--11.8 m³/hr; Minimum--0.8 m³/hr
Pressure Tapping
1/8 in. - NPT
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.