Overview
Combination gas control for use with hot surface/direct spark systems in 120 Vac, gas-fired appliances, with capacities from 30 to 415 cfh.
Features
- Controls include manual valve, two automatic operators and pressure regulator.
- Compact size.
- Provides two automatic valves.
- Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
- Diaphragm-operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted.
- Meets codes requiring dual safety shut-off.
- Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.
- Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure.
- ON/OFF lighting sequence.
- All adjustments, wiring connections and pilot outlet are accessible from top of control.
Product Specifications
- Application
- Single Stage
- Dimensions (in.)
- 5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
- Dimensions (mm)
- 135 mm high x 104 mm wide x 69 mm deep
- Includes
- Two 3/4 x 1/2 in. reducer bushings; Natural to LP Conversion Kit; One 1/2" x 3/8" reducer bushing
- Item Type
- Product
- Mounting
- 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Frequency
- 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Component Recognized MCCZ2.MH5323
- Approvals, Canadian Standards Association
- CSA International: 112395
- Electrical Connections
- 21 in. (533 mm) leadwires.
- Voltage
- 120 Vac
- Operating Temperature Range (F)
- -40 F to +175 F
- Operating Temperature Range (C)
- -40 C to +79 C
- Body Pattern
- Straight-through
- Opening Characteristics
- Standard Opening
- Pressure Ratings (psi)
- 1/2 psi
- Pressure Ratings (kPa)
- 3.5 kPa
- Inlet/Outlet Size (in.)
- 3/4 in. x 3/4 in.
- Pilot Gas Outlet
- None
- Pressure Tapping
- 1/8 in. NPT with plug
- Type of Fuel
- Natural
- Capacity (kBtuh)
- At 1 in. wc p.d.-- 300,000 BTUh: 30,000 BTUh minimum: 415,000 BTUh maximum Natural Gas
- Pressure Regulator
- Standard
- Pressure Regulator Setpoint (in. wc)
- 3.5 in. wc
- Pressure Regulator Setpoint (kPa)
- 0.87 kPa
- Ignition Type
- Direct Ignition
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.