Skip Ribbon Commands
Skip to main content
SharePoint
Login or Register to view pricing and order.
  • Product Info
  • Literature

Overview

The VR8301 continuous pilot gas control is for gas-fired appliances with capacities up to 200 ft3/hr at 1 in. wc pressure drop on natural gas. They Include a manual valve, safety shutoff, single automatic operators & pressure regulator.

Features

  • Straight-through body pattern.
  • Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.

Product Specifications

Application
Single Stage
Dimensions (in.)
5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
Dimensions (mm)
135 mm high x 104 mm wide x 69 mm deep
Item Type
Product
Mounting
0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
Frequency
50 Hz; 60 Hz
Approvals, Underwriters Laboratories Inc.
UL Component Recognized: MH5323
Approvals, Canadian Standards Association
CSA International: 112395
Electrical Connections
1/4 in. quick-connect male terminals
Voltage
24 Vac
Operating Temperature Range (F)
0 F to 175 F
Operating Temperature Range (C)
-18 C to +79 C
Body Pattern
Straight-through
Opening Characteristics
Standard Opening
Pressure Ratings (psi)
1/2 psi
Pressure Ratings (kPa)
3.5 kPa
Inlet/Outlet Size (in.)
No inlet threads x 3/4 in.
Pilot Gas Outlet
Compression fitting for 1/4 in. OD tubing
Pressure Tapping
1/8 in. NPT with plug
Type of Fuel
Natural
Capacity (kBtuh)
At 1 in. wc p.d.-- 180,000 BTUh: 30,000 BTUh minimum
Pressure Regulator Setpoint (in. wc)
3.5 in. wc
Pressure Regulator Setpoint (kPa)
0.87 kPa
Ignition Type
Standing Pilot
Anticipator Setting
0.65 A
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.