Overview

The VR9205Q Direct Ignition Combination 2-Stage Gas Controls are used in gas-fired appliances with up to 140 KBtu/h capacity at 1 in. wc pressure drop. They have been optimized for direct ignition applications and include a manual switch, two automatic operators and a pressure regulator. The valve may be used on either Natural gas or LP gas applications.

Product Specifications

Application
Two Stage
Dimensions (in.)
4.04 in high x 5.04 in wide x 3.2 in deep
Dimensions (mm)
103 mm high x 128 mm wide x 81 mm deep
Includes
6 in. wire harness; LP Conversion Kit
Item Type
Product
Mounting
Any direction
Frequency
50 Hz; 60 Hz
Approvals, Canadian Standards Association
CSA International: 112491
Electrical Connections
1/4 in. quick-connect male terminals
Voltage
24 Vac
Operating Temperature Range (F)
-40 F to +175 F
Operating Temperature Range (C)
-40 C to +79 C
Body Pattern
Straight-through
Opening Characteristics
Standard Opening
Pressure Ratings (psi)
1/2 psi
Pressure Ratings (kPa)
3.5 kPa
Inlet/Outlet Size (in.)
1/2 in. x 1/2 in.
Type of Fuel
Natural (LP if conversion kit included)
Capacity (kBtuh)
At 1 in. wc p.d.-- 140,000 BTUh: 20,000 BTUh minimum at high fire, 8,000 BTU minimum at low fire: 200,000 BTUh maximum at max fire
Pressure Regulator
Adjustment Range: 0.9 in. wc to 4.0 in. wc
Pressure Regulator Setpoint (in. wc)
1.7 in. wc low; 3.5 in. wc high
Pressure Regulator Setpoint (kPa)
0.42 kPa low; 0.87 kPa high
Ignition Type
Direct Ignition
There is no literature attached to this product, please try another material search. If you believe that there should be literature for this product, please contact Customer Care for website support.