Immersion type Aquastat, Unit Pack

L4080B1352/U

Immersion type Aquastat, Unit Pack

  • Product Info
  • Literature

Overview

Immersion type controllers for hydronic heating systems that turn off the burner whenever the boiler water temperature rises to the setpoint.Vertical mounting

Features

  • High Limit Aquastat Controller has adjustable set point.
  • Models available for use with immersion wells or for direct immersion if faster response is needed.
  • A factory-set stop is available on L4080 to prevent setting the control at too high a temperature.
  • Models available with second limit switch to shut off all gas to the burner.
  • Liquid fill in sensing element expands as the boiler temperature rises.
  • At the set point temperature, a diaphragm-actuated snap switch breaks the power supply to the burner primary control.

Product Specifications

Hazmat Information
UN1294, Dangerous Goods in Excepted Quantities, Class 3
Application
Immersion type controllers for hydronic heating systems that turn off the burner whenever the boiler water temperature rises to the set point.
Dimensions (in.)
Insertion depth: 3 in.
Dimensions (mm)
Insertion depth: 76.2 mm
Temperature Range (F)
Maximum--40 F above setpoint or 265 F, which ever is lower.
Temperature Range (C)
Maximum--22 C above setpoint or 129.4 C, which ever is lower.
Includes
Siphon Loop
Mounting
Mount using 1/4 in. NPT female threads or surface mount through base of case
Electrical Ratings
Millivolt--0.25 A @ 0.25 to 12 Vdc; At Full Load-- 8A @ 120 Vac: 4A @ 240 Vac; At Locked Rotor-- 48A @ 120 Vac: 24A @ 240 Vac
Approvals, Underwriters Laboratories Inc.
UL Listed: -models with well, File No. MP466, Guide No. MBPR, -models less well, File No. MP466, Guide No. MBPR2
Operating Temperature Range (F)
100 F to 200 F
Operating Temperature Range (C)
38 C to 93 C
Differential Temperature (F)
8 F
Differential Temperature (C)
4.4 C
Switching Action
Breaks contact on temperature rise to set point.
Approvals, American Gas Association
AGA Design Certified: Test Report 23-11B
Insulation Depth (in.)
1 1/2 in. to 3 in.
Insulation Depth (mm)
38 mm to 76 mm