Dual Direct Ignition Convertible Gas Valve

VR8205R2091/B

Dual Direct Ignition Convertible Gas Valve

This product is no longer available for purchase.

  • Product Info
  • Literature

Overview

Combination gas controls for use with hot surface/direct spark systems in 24 Vac, gas-fired appliances with capacities from 30 to 415 cfh.

Features

  • Controls include manual valve, two automatic operators, and pressure regulator.
  • Provide two automatic valves.
  • Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
  • Diaphragm operated second automatic valve opens under control of the regulator; closes if gas or power supply is interrupted.
  • Meet codes requiring dual safety shutoff.
  • Natural to LP and LP to Natural conversion kits available for standard and slow opening gas valves.
  • All adjustments, wiring connections and pilot outlet are accessible from top of control.
  • ON-OFF lighting sequence.

Product Specifications

Application
Single Stage
Dimensions (in.)
4 5/8 in. high x 4 1/8 in. wide x 2 11/16 in. deep
Dimensions (mm)
117 mm high x 104 mm wide x 69 mm deep
Item Type
Product
Mounting
0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
Frequency
60 Hz
Approvals, Underwriters Laboratories Inc.
UL Component Recognized: MH5323
Approvals, Canadian Standards Association
CSA International: 112395
Customer Special
Nordyne
Electrical Connections
1/4 in. quick-connect male terminals
Voltage
24 Vac
Operating Temperature Range (F)
-40 F to +175 F
Operating Temperature Range (C)
-40 C to +79 C
Body Pattern
Straight-through
Opening Characteristics
Standard Opening
Pressure Ratings (psi)
1/2 psi
Pressure Ratings (kPa)
3.5 kPa
Inlet/Outlet Size (in.)
1/2 in. x 1/2 in.
Pressure Tapping
1/8 in. NPT with plug
Type of Fuel
Natural; LP
Capacity (kBtuh)
At 1 in. wc p.d.-- 150,000 BTUh: 20,000 BTUh minimum
Approvals, Australian Gas Association
Australian Gas Assoc. Design Certificate: 4214; Approved for Delta C Applications
Pressure Regulator Setpoint (in. wc)
3.5 in. wc (natural); 10 in. wc (LP)
Pressure Regulator Setpoint (kPa)
0.87 kPa (natural); 2.49 kPa (LP)
Ignition Type
Direct Ignition
Anticipator Setting
0.5 A