Triple Aquastat Relay for oil applications, vertical case, 1.5 inch insulation depth
Triple Aquastat Relay for oil applications, vertical case, 1.5 inch insulation depth

L8124A1007/U

Triple Aquastat Relay for oil applications, vertical case, 1.5 inch insulation depth

Find Equivalent or Replacement Products.

  • Product Info
  • Literature

Overview

Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems, including domestic hot water service.

Features

  • Immersion-type controllers that combine high limit protection with low limit and circulator control in forced hydronic heating systems.
  • Provide multizone control by using a separate circulator and R845 Relay for each zone.
  • Include diaphragm powerhead and Micro Switch™ assembly that respond to temperature changes in boiler water.
  • Mount directly to boiler.
  • Select models include large transformers and extra terminals for supplying power to low voltage zone valves.
  • Require 24 Vac thermostat with heat anticipator set at 0.2 A (plus current draw of gas valve on L8124E).
  • TRADELINE models include tube of heat conductive compound and range stops.

Product Specifications

Hazmat Information
UN 1294, TOLUENE, 3, II
Application
High Limit Protection, Low Limit and Circulation Control
Dimensions (in.)
6 1/8 in. high x 4 3/8 in. wide x 3 1/16 in. deep
Dimensions (mm)
156 mm high x 111 mm wide x 78 mm deep
Maximum Safe Operating Pressure (psi)
200 psi on outside of immersion well, 100 psi on capsule if inserted directly.
Maximum Safe Operating Pressure (kPa)
1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.
Temperature Range (F)
Maximum--150 F at switches; 265 F at sensing element
Temperature Range (C)
Maximum--66 C at switches; 129 C at sensing element
Includes
No Well
Mounting
Vertical Mount
Approvals, Underwriters Laboratories Inc.
UL Listed (models with well): File No. MP466, Guide No. MBPR; UL Component Recognized (models without well): File No. MP466, Guide No. MBPR2
Approvals, Canadian Standards Association
Certified: File No. LR1620, Guide No. 400-E-O
Operating Humidity Range (% RH)
0 to 95% RH, non-condensing
Voltage
120 Vac
Operating Temperature Range (F)
High Limit-- 130 F to 240 F adjustable; Low Limit-- 110 F to 220 F adjustable
Operating Temperature Range (C)
High Limit-- 54 C to 116 C adjustable; Low Limit-- 43 C to 104 C adjustable
Differential Temperature (F)
High limit : 10 F fixed; low limit: 10-25 F adj.
Insulation Depth (in.)
1 1/2 in.
Insulation Depth (mm)
38 mm
Electrical Ratings, Burner
At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac
Electrical Ratings, Circulator
At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac