24V 1/2 in Sweat N.C. Zone Valve

V8043E5004/U

24V 1/2 in Sweat N.C. Zone Valve

  • Product Info
  • Literature

Overview

Two-way on-off low voltage valves consist of an actuator and valve assembly for controlling the flow of hot water.

Features

  • All models may be installed without disassembling the valve.
  • Compact construction for easy installation.
  • Manual opener (on all models, except straight-through, normally open valves) for valve operation on power failure; valve returns to automatic position when power is restored.
  • Complete powerhead may be removed or replaced without breaking plumbing line connections or draining the system.
  • "Quick Fit" pushbutton powerhead makes it easy to remove for service.
  • Series 5000 replacement powerhead is backward compatible with series 1000 zone valves.
  • Innovative motor technology offers silent operation, water hammer resist and longer life.

Product Specifications

Application
Hydronic Control
Dimensions (in.)
4 3/8 in. high x 3 1/2 in. wide x 2 3/8 in. deep
Dimensions (mm)
111 mm high x 89 mm wide x 60 mm deep
Comments
Use this valve in closed loop hydronic systems that do not contain dissolved oxygen in system water, such as fresh water from frequent source of makeup water. Valve designed for cycling (not constantly powered on) applications.
Frequency
60 Hz
Approvals, Underwriters Laboratories Inc.
Approvals, Canadian Standards Association
CSA Certified: File 1322
Operating Humidity Range (% RH)
5 to 95% relative humidity, non-condensing.
Voltage
24 Vac; Power Consumption--7.2 VA
Ambient Temperature Range (C)
52 C Maximum
Ambient Temperature Range (F)
125 F Maximum
Connection Type
Sweat
Electrical Connections (in.)
18 in. leads
Electrical Connections (mm)
457 mm leads
Timing
Nominal Open--15 sec
Body Pattern
Two-way, Straight-through
Pipe Size (inch)
1/2 in.
Pipe Size (DN)
DN15
Current Draw
0.32A
Fluid Temperature (C)
10 C to 93 C
Fluid Temperature (F)
50 F to 200 F
Maximum Differential Pressure Ratings (Close-off) (psi)
20 psi
Maximum Differential Pressure Ratings (Close-off) (kPa)
138 kPa
Capacity (Cv)
3.5 Cv
Capacity (Kv)
3 Kv
Valve Action
Spring return to close
Valve Type
Zone Valve
Materials (Body)
Brass
Materials (Seat)
Brass
Materials (Stem)
Stainless Steel
End Switch Rating
50 VA pilot duty @ 24 V; 4.4 A running with 26.4 A inrush @ 120 V
Actuation
Two position
De-energized Position
Normally Closed
Auxiliary End Switch
N.O. SPST
Static Pressure Rating (psi)
300 psi
Static Pressure Rating (kPa)
2068 kPa
Materials (Plug/Ball/Disc)
Buna-N (NBR) Rubber Ball
Materials (Packing)
EPDM O-rings
Manual Opener
Yes

Marketing Collateral

Sales/Promotional Materials-Sales Ad for V8043, V8044 Zone Valves with Removable Powerhead (English)

Sales/Promotional Materials-Sell Sheet 5000 Series Zone Valve (English)

Sales/Promotional Materials-Brochure for V8043 1000 Series Zone Valve (English)

Product Selections/Comparisons-New V8043 5000 Series Zone Valve Advantage

Sales/Promotional Materials-Count on One Brand For a Full Line of Hydronic Heating and Potable Water Solutions

Sales/Promotional Materials-V8043 5000 Series Zone Valves (French)

Sales/Promotional Materials-Resideo Hydronic Heating Solutions Brochure (English)

Sales/Promotional Materials-Mixing Valve Selection Guide

Sales/Promotional Materials-Resideo Hydronic Heating Solutions Brochure (French)

Sales/Promotional Materials-Sell Sheet 5000 Series Zone Valve (Spanish)

Sales/Promotional Materials-Sell Sheet 5000 Series Zone Valve (French)

Wiring-Motorized Valve

Wiring-Oil & Hydronic Training

Wiring-Existing White Rodgers System

Wiring-Wiring V8043E to White Rodgers system

Wiring-Wiring V8043F to White Rodgers system

Wiring-Wiring V8043F to White Rodgers system

Wiring-V8043 operation for normally closed valve

Wiring-Typical wiring for V8043F

Wiring-Typical wiring for V8043E and V8044E

Wiring-Typical 3-Zone system

Wiring-Existing Taco System

Wiring-Wiring Honeywell V8043F to Taco system

Wiring-Wiring V4043E to Dole system and Flair System

Wiring-Wiring V8043F to Dole System and Flair System

Wiring-Existing Dole system

Wiring-Existing Flair System

Wiring-Typical 4-zone system

Wiring-Oil & Hydronic Training

Wiring-Oil & Hydronic Training

Wiring-Oil & Hydronic Training

Wiring-Oil & Hydronic Training

Dimension-Motorized Valve

Dimension-V8043 5000 Series QuickFit Zone Valves

Dimension-Two-Way On-Off Low Voltage Valve

Dimension-5000 Series QuickFit Zone Valve

Technical Documents

Installation Materials-Installation Instructions for V4043, V4044, V8043, V8044 Fan Coil Valves; Zone Valves (English)

Maintenance/Product Reference Materials-White Paper for V8043 To Install a 5000 Series Actuator on a 1000 Series Valve Body (English)

Product Data and Specifications-Product Data for V4043, V4044, V8043, V8044 Motorized Valves (English)

Installation Materials-Zone Valve Sticky-Back Labels - Legacy Product Document

Product Data and Specifications-Submittal Sheet for V8043 5000 Series Zone Valves (English)

Installation Materials-Installation Instructions for V4043, V4044 Valves; V8043, V8044 Zone Valves (English, French)