Electric Heater Relay W. DPST Switching

R8229A1005/U

Electric Heater Relay W. DPST Switching

Find Equivalent or Replacement Products.

  • Product Info
  • Literature

Overview

Normally Closed Relays And Contactors For Load Control Systems.

Features

  • Close and leave load operating in case of wiring or control problem, or relay malfunction.
  • Consume no power while load is powered; require power only to shed load.
  • Operate directly from a pilot duty rated relay in the load control system.

Product Specifications

Dimensions (in.)
2 3/16 in. high x 2 3/32 in. wide x 2 1/4 in. deep
Dimensions (mm)
56 mm high x 53 mm wide x 57 mm deep.
Item Type
Product
Frequency
60 Hz
Approvals, Underwriters Laboratories Inc.
UL Component Recognized
Approvals, Canadian Standards Association
Recognized
Electrical Connections
#10 combination head screws
Temperature Ratings (C)
-40 C to +74 C
Temperature Ratings (F)
-40 F to +165 F
Switching
DPST
Contact Ratings (AFL)
2.8 A @ 600Vac; 3.5 A @ 480Vac;7.0 A @ 120 Vac, 208 Vac, 240 Vac, 277 Vac
Contact Ratings (ALR)
14 A @ 600 Vac; 17.5 A @ 480 Vac; 35 A @ 120 Vac, 208 Vac, 240 Vac, 277 Vac
Contact Ratings (resistive)
10.0 A @ 600 Vac; 12.5 A @480 Vac; 25 A @ 120 Vac, 208 Vac, 240 Vac, 277 Vac
Coil Ratings Voltage
24 Vac