Skip Ribbon Commands
Skip to main content
SharePoint
Login or Register to view pricing and order.
Item 2 Of 5
Aquastat Relay, 180 – 240 F range with 15 degree F fixed differential
Aquastat Relay, 180 – 240 F range with 15 degree F fixed differential

L8148E1265/U

Aquastat Relay, 180 – 240 F range with 15 degree F fixed differential

This product is available in the US only.

  • Product Info
  • Literature

Overview

Immersion-type controllers that combine high limit protection with switching relay control of burner and circulator motors.

Features

  • High limit opens burner circuit only.
  • Select models include transformer and accessory terminals for adding a remote low limit controller.
  • Case available for horizontal or vertical mounting.
  • Requires a 24 Vac thermostat with heat anticipator set at 0.2A.
  • TRADELINE models include well adapter, tube of heat conductive compound and range stops..

Product Specifications

Hazmat Information
UN 1294, TOLUENE, 3, II
Application
High Limit
Dimensions (in.)
6 1/8 in. high x 4 5/16 in. wide x 3 1/8 in. deep
Dimensions (mm)
156 mm high x 110 mm wide x 79 mm deep
Maximum Safe Operating Pressure (psi)
Immersion Well: 255 psi
Maximum Safe Operating Pressure (kPa)
Immersion Well: 1757 kPa
Temperature Range (F)
Maximum--150 F with 1.2 A 24 V load; 77 F with 1.4 A 24 V load
Temperature Range (C)
Maximum--66 C with 1.2 A 24 V load; 25 C with 1.4 A 24 V load
Includes
Molex® plug for use with vent damper, includes heat-conductive compound.; Molex(r) plug for use with vent damper, includes heat-conductive compound.
Mounting
Vertical Mount
Electrical Ratings
Low Voltage: 0.8 A max. @ 24 Vac; 0.25 A @ 0.25 to 12 Vdc; At Locked Rotor-- 44.4A @ 120 Vac: 22.2A @ 240 Vac
Frequency
60 Hz
Approvals, Underwriters Laboratories Inc.
UL Listed: File No. MP466, Vol. 13, Sec. 2, Guide No. MBPR2.
Approvals, Canadian Standards Association
Certified: File No. LR95329-1
Tradeline Value
Tradeline
Electrical Connections
Quick-Connect / Screw
Operating Humidity Range (% RH)
0 to 95% RH, non-condensing
Voltage
120 Vac
Operating Temperature Range (F)
High Limit-- 180 F to 240 F
Operating Temperature Range (C)
High Limit-- 82 C to 116 C
Differential Temperature (F)
15 F fixed
Switching Action
SPST: High Limit & Circulator
Anticipator Setting
0.2 A
Capillary Length (in.)
4 1/2 in.
Insulation Depth (in.)
1 1/2 in. to 3 in. less well
Insulation Depth (mm)
38 mm to 76 mm less well
Capillary Length (mm)
114 mm
Electrical Ratings, Burner
At Full Load-- Low Voltage: 0.8 A max. @ 24 Vac: Line Voltage: 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- Line Voltage: 44.4 A @ 120 Vac: 22.7 A @ 240 Vac
Electrical Ratings, Circulator
At Full Load-- 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor-- 44.4 A @ 120 Vac: 22.2 A @ 240 Vac